Three-phase Combination Lightning Arrester / Surge Arrester 3 phases / Transient Voltage Suppressor
1,Anti-leakage trace, anti-corrosion, resistance pollution, good hydrophobicity
2,Three-phase Combination Lightning Arrester
Key words : Three-phase Combination Lightning Arrester / Surge Arrester 3 phases / Transient Voltage Suppressor
Companies with a full set of advanced production and testing equipment, product quality in the industry to stay ahead, have passed ISO9001-2000, CE, ROHS certification and so on.
Service conditions:
Ambient temperature:-40oC~+40oCAltitude: not more than 3000mMax wind velocity:lower than 35m/sMax horizontal pull N(The top wire of the arrester):147NLong time force the power frequency voltage to the arrester is lower than the products Continual operating voltage.Excellence in product quality and quality of services, cooperation was more than excellent suppliers.
Three-phase Combination Surge Arresters :the international standard type compared with common old type,the referrence sheet is as below:
System rated voltage | International standard type | Common partial old type | Application place |
6KV | YH5WZ-10/27X2 | TBP-B-6.3 TCB-Z/6.3 | Power station type |
10KV | YH5WZ-17/45X2 | TBP-B-10.5 TCB-Z/10.5 | |
35KV | YH5WZ-51/170X51/134 | TBP-B-35 TCB-Z/35 | |
6KV | YH5WZ-10/27X2 | TBP-C-6.3 TCB-R/6.3 | For use of shunt compensation capacitor bank |
10KV | YH5WZ-17/45X2 | TBP-C-10.5 TCB-R/10.5 | |
35KV | YH5WZ-51/170X51/134 | TBP-C-35 TCB-R/35 |
The technology parameter of Three-phase Combination of Surge Arrester is as below:
Type Number | Rated system voltage(KV) | Rated voltage of Surge Arrester | Line connection method | Continuous ooperating voltage(KV) | DC 1mA refer voltage(KV) | Power frequency refer voltage(KV) | Residual voltage under norminal discharge current(KV) | 2 ms squre wave shocked withstand current(KA) | Application place |
YH5WZ-10/27X2 | 6 | 10 | Phase-Phase | 8.0 | 15.0 | 11.5 | 27 | 400
| Power station type |
Phase-Ground | 14.4 | 10.0 | 27 | ||||||
YH5WZ-17/45X2 | 10 | 17 | Phase-Phase | 13.6 | 25.0 | 18.0 | 45 | 400
| |
Phase-Ground | 24.0 | 17.0 | 45 | ||||||
YH5WZ-51/170X51/134 | 35 | 51 | Phase-Phase | 40.8 | 88.0 | 59.0 | 170 | 500
| |
Phase-Ground | 73.0 | 51.0 | 134 | ||||||
YH5WR-10/27X2 | 6 | 10 | Phase-Phase | 8.0 | 15.0 | 11.0 | 27 | 400
| For use of shunt compensation capacitor bank |
Phase-Ground | 13.8 | 10.0 | 27 | ||||||
YH5WR-17/45X2 | 10 | 17 | Phase-Phase | 13.6 | 25.0 | 18.0 | 45 | 400
| |
Phase-Ground | 23.0 | 17.0 | 45 | ||||||
YH5WR-51/170X51/134 | 35 | 51 | Phase-Phase | 40.8 | 88. | 59.0 | 170 | 500 | |
Phase-Ground | 73.0 | 51.0 | 134 |